The term churn refers to a pump that is
|
running but all discharges are closed
|
|
Which of the following fire pumps is driven by an electric motor installed on top of the pump?
|
Vertically mounted split-case pump
|
|
Which of the following parts of the controller for electric drivers provides overcurrent protection by opening if too many amps are being drawn?
|
Circuit breaker
|
|
A flow test of the pump assembly is required
|
annually
|
|
Primary performance criteria standards for fire pump testing are contained in
|
NFPA 20
|
|
What is the purpose of a speed governor on a steam turbine controller?
|
Maintain the rated speed for the maximum pump load
|
|
Why are there so may indicating valves in a fire pump installation?
|
provide the ability to isolate components
|
|
Which of the following statements about diesel engines is most accurate?
|
They are usually more expensive than electric drivers
|
|
If a manufacturer's reccomendations are not available for a preventative maintenance program, adopt a program that adheres to
|
NFPA 25
|
|
Fire pump units that are located outdoorsor in buildings other than the building being protected must be located at least
|
50 feet away from the protected building
|
|
Which of the following parts of the controller for electric drivers indicates when power is available to the pump control panel?
|
Pilot lamp
|
|
Only qualified personnel should service the pump controller because of
|
high-voltage wiring
|
|
Which of the following statements about vertical-shaft turbine pumps is most accurate?
|
The shaft can be water lubricated or oil lubricated
|
|
On a diesel engine the tachometer indicates the
|
revolutions per minute (rpm) of the engine
|
|
Which of the following parts of the controller for electric drivers is used to shut off the motor after the situation has returned to normal?
|
Running period timer
|
|
Which of the following types of pump drivers is the least acceptable for use with modern fire pumps?
|
gasoline engines
|
|
Which of the following statements about electric motors is most accurate?
|
They require a relatively small amount of maintenance
|
|
Which of the following components has the purpose of preventing pressures from reaching levels that are high enough to damage system piping or fittings?
|
Relief valve
|
|
Indoor fire pump units must be
|
seperated from all other areas of the building by fire rated construction
|
|
Which of the following components is used to prevent false starts and maintain constant pressure on the fire protection system?
|
Pressure maintenance pump
|
|
Which of the following fire pumps is most likely to use a well or underground storage tank as a water source?
|
Vertical-shaft turbine pump
|
|
The only suitable application for steam turbines is when an uninterrupted supply of steam is available
|
in sufficient quantities and at sufficient pressure
|
|
If the pump room is not constantly attended, alarm signals should be
|
transmitted to a constantly attended location
|
|
A diesel engine is required to have an adjustable governor to maintain engine speed within a
|
10 percent range
|
|
Which of the following fire pumps is a variation of the horizontal split-case design and is a single-stage pump that has a centerline suction and discharge?
|
End suction pumps
|
|
On a diesel engine controller if the pump is the sole supply to standpipes or sprinkler systems, the automatic start controller should
|
be wired for manual shutdown
|
|
Which of the following statements about diesel fuel is most accurate?
|
Diesel fuel is not as volatile as gasoline
|
|
Aboveground pipe must be constructed of
|
steel
|
|
At minimum, how long should diesel engines be operated?
|
30 minutes
|
|
At a minimum, how often should pumps be operated?
|
weekly
|
|
The battery charger for a diesel engine must be capable of fully recharging the batteries within
|
24 hours
|
|
The casing for the shaft and impeller can be seperated exposing the shaft, bearing, and impeller in
|
split-case pumps
|
|
Which of the following parts of the controller for electric drivers turns on the fire pump if the water pressure on the system drops below the switch setting?
|
Pressure switch
|
|
More modern pump installations
|
are equiped with a metering device for testing
|
|
What is the purpose of a pressure maintenance pump?
|
Prevent false starts
|
|
Which of the following fire pumps is most likely to be commonly installed in all occupancy types?
|
Horizontal split-case pump
|
|
Which of the following statements about horiozontal split-case pumps is most accurate?
|
horizontal split-case pumps are the most common of the split-case pumps
|
|
When pumps require only a single gauge, it will be located
|
on the discharge line
|
|
When operating against a closed system, or at churn, a pump must not develop more than
|
140 percent of its rated pressure
|
|
Which of the following fire pumps is a single-stage pump designed to fit into the intake/discharge line and has operating pressures up to 165 psi?
|
Vertical inline pump
|
|
Which of the following statements about piping is most accurate?
|
Larger piping reduces the frictions loss and increases the pressure available at the pump
|
|
All current-carrying parts of a controller for an electric motor-driven pump should be at least
|
12 inches off the floor
|
|
No standard fire pump is permitted to have a pressure rating less than
|
40 psi
|
|
The most common means of starting diesel engines for fire pumps are
|
batteries
|
|
What is the purpose of the strainer on a vertical-shaft turbine pump?
|
Keep out fish, snails, leaves and other objects
|