24 Cards in this Set
- Front
- Back
What type of pipe is used on gas pipe?
|
Black pipe
|
|
What should be used on the gas pipe fittings to prevent leaks?
|
Piping compound
|
|
What are three components that must be installed in the gas pipe before hooking into the gas valve?
|
1. Union
2. Drip leg 3. Shut–off |
|
What is the purpose of a drip leg on the gas line? |
Prevents debris and moisture from entering gas valve
|
|
How long and how much pressure should be held in the gas pipe to make sure they are not leaking?
|
3 psig for 10 min
|
|
If a gas line is sized too small, this will create a _______ ____ to the gas valve.
|
Pressure drop
|
|
What type of pipe should be used to run flues?
|
B–type
|
|
Why should running flues horizontally be avoided?
|
Condensation build up
|
|
How much of a rise should be in flue pipe run horizontally?
|
1/4 inch per foot
|
|
When a B type pipe goes through a ceiling or floor how much clearance should the pipe have between it and combustible materials?
|
1 to 3 inches
|
|
Single wall pipe should have ______ clearance from combustible material.
|
6 inch
|
|
When hooking two flues to a common flue, is the smaller flue hooked in above or below the bigger flue?
|
Above
|
|
Should a connector vent be placed as high or as low on the common vent as possible?
|
High
|
|
What are the names of the PVC pipes that are used for the high efficiency flue?
|
Intake and Exhast
|
|
Why must a mid–efficient furnace in a confined furnace room be vented?
|
Combustion
|
|
Where should the two vents be located in a furnace room to provide proper venting?
|
Floor and Ceiling
|
|
What must be used to properly charge a central air conditioner?
|
Charging chart
|
|
Where will the charging chart be located on a central air conditioner?
|
On back or cover of control panel
|
|
What method is used with the charging chart to charge a system with a fixed orifice?
|
Super–heat
|
|
What method is used with a TXV valve?
|
Subcooling
|
|
What are the design temperatures and humidity used on central air conditioners?
|
75 Degrees and 50%
|
|
When checking a charge it is found that the actually super–heat is 8 ํ lower than what the charging chart recommends, would refrigerant be added or removed?
|
Removed
|
|
What does it mean to balance the duct system?
|
Stop uneven Temps and have proper C.F.M.s
|
|
How is the duct system adjusted to get the proper air flow to the rooms?
|
Dampers
|