  • Front
  • Back

A boiler rated for hot water service at 120 (psig) and 240F maximum would be constructed under the rules of which code?

ASME section IV

Which directive boiler is built with a firebox that is not completely surrounded by water?

Firebox boiler

Which boiler consists of an arrangement of drums and headers interconnected by tubes?

Watertube

How many fans are used to control the draft through a balanced draft boiler?

Two: one on the inlet and one on the outlet

Which boiler would be classified as a firebox boiler?

HRT

What is the minimum clearance required in front of an access panel on a gas-fired boiler?

24” regardless of whether it is insulated or not

What does the installer have to do with the boiler and piping systems before turning them over to the owner?

Inspect and test for leak tight service

What is the cause of the most common problems encountered after start-up of steam boilers and systems?

Improper cleaning and flushing

What is likely to occur if there is a heavy concentration of dissolved or suspended particles in the boiler water?

The water may foam and could cause priming

What should be done if the water in the sight glass is not clear after cleaning and flushing?

Repeat the cleaning procedure

What should be done with the results of all pertinent test results during the test, start and balance phases of system start up?

Record the results and have the results verified

Where is the appliances gross rating taken?

Boiler nozzle outlet

Where is the appliances net rating taken?

Heat emission units

What does the term pass in a boiler terminology mean?

The number of times the products of combustion travel the length of the boiler is

What is the main advantage of steam over hydronic systems?

Speed of transmission

What is the usual maximum circulation speed of water for a low temperature hot water heating system?

4 feet per second

What does load tracking refer to when discussing boilers?

The ability of a boiler to respond to changes in steam or hot water demand

Which boiler had the ability to respond to sudden demands of large volumes of steam for a short period of time?

Firetube

Which boiler has the ability to handle wide variations in load over a long period of time?

Watertube

Why is clean condensate considered to be ideal for feeding back into the boiler?

Condensate is essentially distilled water, so it contains no dissolved solids

How often should a pop test be done on a safety valve used in an LP steam heating boiler?

Annually

What is the suggested method of determining whether water is flowing through a water feeder valve?

Listen with a stethoscope

What is the most probable cause of the water level in a gauge glass fluctuating rapidly?

Foaming or priming inside the boiler