What is the minimum dimension of a chimney if it is not round?

2”

What is the minimum size diameter of a vent or vent connector?

3”

What is the purpose of the General Venting Requirements?


To adjust the sizing tables to reflect variations in the installation

When using rule of thumb sizing , how is the size of the vent connector serving a single appliance determined?

It’s always the same size as the draft hood outlet

When using ROT , how is the size of the vent connector serving a single appliance with multiple draft hood outlets determined?

It’s the combined area of all outlets

When using ROT sizing what is the minimum size chimney serving a single appliance ?

One size larger than the vent connector

Using ROT what is the formula used to Size a vent serving multiple appliances ?

100% of the area of the largest appliance output and 50% of the sum of the additional outlet areas.

What is the minimum size (area) of a chimney?

12 inches square

What is the maximum size of a masonry chimney for a given installation?

Not to exceed the appliances input by more than 25%

Do the self test questions

**** face

What is the smallest size opening grille used for air supply?

1/4”

What is the minimum distance above grade for an air supply inlet?

12”

Where must the combustion air pot be located when the total appliance input is less than 400 MBH?

Within 1 foot above and 2 feet away from the largest appliance burner.

When air supply is brought into the mech room by the through a transfer grill from type B ( loose construction) building , how is the size of opening calculated ?

The opening shall not be less than 1”sq for every 1000 BTU’s if appliance input.

Where would the transfer grill in the last question be located ?

Between 12” and 18” off floor level.

How is , in a draft hood hood appliance in a loosely constructed building , air supply sized?

Two openings , one off the floor and one opening close to the ceiling sized 1 in sq for each 1000 BTU of appliance input

Category 1 appliances installed in an enclosure have a total input of 525,000 BTU’s . What size of outdoor air supply is needed?

75 sq inches

What is the formula to determine for Air supply sizing for appliances more than 400MBH?


1sq”for every 7000 BTU up to a million.


Any BTU over that million is 1 sq” for every 14000 bTU.


Add the two together for the total square inches.

What size of outdoor combustion air supply is required for a power burner appliance with 1,500,000 BTU’s?

1,500,000/30,000= 50 sq”

How is VENTILATION Air for appliance installations over 400MBH sized?

It is sized at 10% of the air supply size but not larger than 10” square

What is the smallest area allowed for a square or rectangular air supply?

9inches square

What is the smallest dimension of a square or rectangular air supply ?

3X3”

What is the formula for sizing air supply for Power Burner appliances ?

1 square inch for every 30,000 BTU

Using ROT, what size of vent is required for a single appliance with a draft hood outlet of 4” diameter ?

4”, same size as the draft hood outlet

A draft Hood appliance with a 5”outlet and a draft hood appliance with a 3” outlet are connected to a common vent through separate vent connectors. Using ROT what size is the vent for this?

5X5=25


3X3=9/2=4.5


25+4.5=29.5


6X6+36”


6”

A venting system has a common vent connector and common vent offset . How much would the values in the vent sizing tables be reduced ?

A total of 30%

TOT

Total of 30%

How much reduction of the vent sizing table is required for a corrugated chimney liner?

20%

ROT vent sizing methods only apply to _________ appliances

Natural Draft Hood

ROT sizing method for single appliance connected to a chimney

Vent connector same size as draft hood and chimney shall be one size larger.

ROT sizing method for two or more appliances connected to a chimney:

Each appliance the same as draft hood and chimney is the 100% the size of the largest and 50% of the area of the other appliances .

The ROT method for a COMMON VENT CONNECTOR :


Area of common vent is equal to 100% of the area of All the appliances

What is required when a mechanical air supply duct is used?

The mechanical unit must be interlocked with the appliance it serves.

A vent terminal must be at least ________ feet above any obstruction within ______feet of the terminal

2


10

A chimney terminal must be at least _____ feet above a roof and at at least ______ feet above any obstruction within _____ feet.

2


3


10

The minimum gauge material used for a vent connector must be ____________ or ________. If no dilution Air is entrained the minimum guage is _____ and must be at least ______ for an incinerator.

28 GSG


22!B&SG


24 GSG


20 GSG

A ventilated thimble must be at least 4” larger than the vent connector if it is less than ______ feet long.

6

A ventilated thimble must be must be ____larger than the vent connector if it is more than _____ feet long.

2”


6

The DP column must be used to size a vent connector or vent in an air tight building when ________ appliances are installed.

Draft Hood

Category II, III and IV appliances are sized by ________________, not the code

Manufacturers certified instructions


Table

Combustion/Dilution Air requirements for appliances having DRAFT CONTROL DEVICES with a combined input up to 400,000 BTU


Always use round column

Table 8.2

Combustion air requirements for appliances NOT having draft control devices when the combined input is up to 400MBH


Always use round pipe column

Table C.1

Capacity of type B vents with B-Vent connectors serving a single category 1 appliance.

Table C.2

Capacity of B-vents with single wall ( c vent) vent connectors serving a single Category 1 appliance.

Table C.3

Capacity of type B double wall vents with Type B double wall vent connectors serving two or more category 1 appliances

Table C.4

Capacity of double wall ( B VENT) with Single wall (C VENT) vent connectors serving 2 or more category 1 appliances .

Minimum clearance for single wall ( c vent ) is _____”. For double wall (b vent ) it is __”.


C Vent clearance may be reduced to ___” if combustibles are protected.

6”


1”


2”

Special Venting Systems used for category 3 and 4 appliances must be certified to the ____/____ standard.

CSA/ULC S-636

Types of piping allowed for category 2,3 and 4 appliances

Stainless Steel


System 636

Max allowable pressure drop for category 1 appliances?

5 pascal, -0.02” (-0.5mm)

The resistance of a 90• elbow is equivalent to ______’

10 feet

Each additional elbow installed to the vent connector requires the tables to be reduced ____% for draft hood appliances

10%

Each additional elbow installed to the vent connector requires the tables to be reduced ____% for fan assisted appliances

15%

Whenever the vent connectors from two or more appliances (common header), the reduction will be _____%

10%

Length of the header or common vent connector manifold should not exceed ______ for each inch of diameter.

1.5’

An offset results in a reduction of _____ or 2 elbows.

20%

If an appliance is not rated for high altitude it must be de-rated by____%

10%

Chimney liners result is a reduction of ______%

20%