Rising stem valves are used most often

in pump stations

When a bacteriological water sample comes back marked "positive" you should immediately

resample the same location and 1 each within 5 connections upstream and downstream

A connection between a safe and an unsafe water supply is

A cross connection

The number of distribution system samples that must be taken each month is based on

the population and/or number of services

The primary reason for a dry barrel fire hydrant is

to prevent freezing

Positive displacement meters are the ______ and ______type

disc / piston

The typical daily water usage in gallons per capita per day (gpcd) is about

100 to 200

A new section of water main has series of things that must be done to it before completely backfilling and putting it into service. What is the proper order for doing them?

1. Pressure test


2. flush


3. disinfect


4. flush


5. collect bac"t" samples

Shut-off valves in residential area should be located at least every

800 feet

The average water loss )per AWWA) due to leakage in most systems is

5 to 10%

Service lines that connect the consumer to the water system usually range from

3/4 to 1 1/2"

There are several considerations to be taken into account when installing a routine bacteriological sample station. Out of the following, which would you choose?

At a point in the distribution system representative of that area.

The killing of pathogenic organisms is called

disinfection

If you went to a customer's service to turn the water off (lock-off) for non-payment, the valve you would most likely use would be the

angle meter (curb) stop

When operating valves there are two main problems that can occur (besides a stuck or broken valve). One is water hammer, the other is

cavitation

When operating a dry barrel fire hydrant it is important to operate with the valve fully open to allow

seal off drain hole

Sodium thiosulfate neutralizes ______ in water samples.

chlorine

When the flow into a reservoir is set about the same as the average demand then the reservoir is said to be

floating

Water is considered to be ____ if it's chemical, physical, and bacteriological characteristics make it satisfactory for drinking.

potable

Normally a distribution reservoir will contain _____hours of "peak period" demand.

8 to 12

The dafe yield for a well is the amount of water that can be pumped from the aquifer over period of time that includes

the driest year

When pressure testing a new "CCCL" water main you should fill it first and wait at least

24 hours

Dissolved iron in a public water supply system may cause

a red water problem

A system that uses a sealed tank that is partially filled with air that is compressed in order to supply water pressure to a service area is called a(n).

hydropneumatic system

If a bacteriological sample cannot be analyzed within _____ it should be refrigerated.

1 hour

"Force" is a problem with many valves used in a water system. A valve that is commonly used in larger sizes that does not suffer the effects of force is the

butteryfly valve

In waterworks terminology the word "residual" is used to describe

The amount of chlorine or other disinfectant available for continued disinfection

The USEPA sets primary and secondary standards for water. The primary standards are related to _____ and the secondary standards are related to __________.

health / aesthetics

The resistance to flow of water in a pipe is called

friction

The use of meters on consumer services has led to

reduced usage

Air release valves are installed on the

top of water main

Which of the following meters has no moving parts>

venturi

The term "water table" is used to describe

the level to which the soil or rock voids are saturated with water

If source water contains toxic agents in it that make it hazardous, it is considerd

contaminated

A venturi meter determines flow by comparing the pressure at the throat and a point just _____of the throat.

upstream

MCL stands for

Maximum Contaminant Level

Deposits in cast iron water mains are called

tubercles

A high "C" factor number indicates that a pipe

has a smooth interior

A toxic substance is always

poisonous

"Clear Wells" are used to store water from

uncontaminated streams

When collecting a water sample for bacteriological testing, you should

flush long enough to clear the sample line

Two conditions that could cause a backflow are

backpressure and backsiphonage

Positive pressure in the main is a

consideration for water quality

Any vertical wall trench ______ or deeper must be shored

5 feet

The amount of pressure pushing downward on the outside of a pipe from the earth covering it is called

the "squeeze"

The use of wells in a distribution system can decrease the needs for

operational storage reservoirs

When drawing a bacteriological sample it is important not to

1. contaminate the bottle


2. rinse out the sodium thiosulfate


3. fill it to the very top (no air)

"Thrust" is a condition that will occur at

any change of direction in the pipe

A gate valve

is the most common isolation valve in a distribution system.



The "cone of depression" is the

area of a well's water table that is dewatered during pumping.

Milky looking water is usually a result of

air trapped in the water

Consistent pressure in a distribution system reservoir

the greater the chance for residual degradation and bacterial growth

the longer water remains in a distribution reservoir

the greater the chance for residual degradation and bacterial growth

Cholera, typhoid, dysentery, and diarrhea are the most common

water related illnesses

An altitude valve is used to

measure the feet above sea level

__________ is the most common method of well construction

Drilling

The term "drawdown" is the elevation difference between the _______ and the ________.

static water table / level during pumping

When distribution valves are opened and closed rapidly

it can cause a dangerous condition known as "water hammer"

The AWWA recommends that 5/8 water meters be tested once every

5 to 10 years

The hardness of water is

not a health related issue.

The hydraulic grade line is the elevation _________ that water would rise to at a given point in a distribution system.

"Above sea level"

The carrying capacity of a water system can be improved by

looping the water lines

_________ is the minimum pressure that should be allowed in a distribution system, even during fire fighting.

20 psi

New service connections can be made on a "live" water line by making a

"hot tap"

Globe style vavles (is Cla-Valves) are mainly used for

pressure and flow regulating

Pathogenic bacteria is considered

harmful to humans

The main use of gate valves in the distribution system is for

isolation

How long does it take to get results for a Colilert bacteria test?

24 hours

Small flow meters are usually displacement meters, and large flow meters are usually

velocity meters

Drinking water standards are categorized as

primary and secondary

Concrete coated cement lined steel cylinder pipe is most commonly used for

larger transmission lines

Reservoir drains and overflows are plumbed

with an air gap separating them from storm drains or culverts

Water and sewer mains are installed

with 10' horizontal separation and a 1' vertical separation

If a trench cannot be shored for some reason, then

the sides should be sloped

After emergency repairs a water main can be chlorinated to _________ to reduce the required contact time to _________.

300 mg/l / 15 min

_________ is the preferred distribution disinfectant to aid in the control of THM's.

Chloramines

Large gate valves sometimes have a small by-pass installed around them. What is the purpose of this by-pass?

To equalize the pressure on both sides after shutdown.

Aesthetic aspects of water deal with

taste, color, and odor.

Water mains are disinfected

after they have been installed.

AWWA standards require positive displacement meters to read

within 98.5% to 101.5%

Pressure regulating stations are used to

decrease high pressure to a steady lower pressure

The type of meter most commonly used for varying assemblies are

installed above ground at a high point in the main.

As a common practice, air release and vacuum valve assemblies are

installed above ground at a high point in the main.

"Hardness" in water is generally caused by

calcium and magnesium

The "Zone of Influence" refers to the

distance that the cone of depression affects the normal (static) water level.

A positive displacement meter is usually used on a service that has

low flows

When taking a bacteria (coliform) sample it is important that the operator

not contaminate it

The AWWA has standards for accuracy requirements for new meters of various types. What are the accuracy requirements for a new positive displacement type meter at normal flow rates?

97 - 103%

The resistance to flow of water in a pipe is called

friction

In determining the purity of a water sample, it is usually tested for the presence of coliform bacteria because

its presence indicates that the water may have been contaminated

The primary purpose of distribution system storage (reservoirs) is

to supply water at peak demands.

The person in your department that is responsible for being sure that your department has a good record keeping system is

the supervisor

The maximum withdrawal rate from 150 lb chlorine cylinder is

40 lbs / day

The carry capacity of a water main can be reduced by

tubercules

The primary reason to install a dry barrel type hydrant (other than fighting fires) is

to prevent freezing

A _______ type pump must never be started against a closed discharge valve.

centrifugal

You are to dig a trench about 4.5 feet deep to install a pipe in. As you are digging you find that the soil is very loose. You are unable to slope the trench due to near-by utilities. What will help you shore this type of trench?

Use plywood sheeting with the jacks

As water meters age, they tend to

under read

When installing new packing rings in a pump you should

stagger the joints

The device installed on a pump shaft that causes the water to be (moved) forced out against the case is called the

impeller

When disinfecting a new water main, the chlorine residual must not drop below _______ for at least ________.

25 mg/l , 24 hours

If a water sample cannot be analyzed within _______ it should be refrigerated.

1 hour

The most frequently reported cause of waterborne disease in the U.S. is

cross-connections

A standard measurement of electrical power is the

watt

The pressure exerted downward on a water line from the soil covering it is known as the

load

When testing for chlorine residuals, the reagent most used is

DPD

A new section of water line has been laid. Before it is completely backfilled and put into service, several things must be done. What is the proper order for doing them?

1. Pressure test


2. Flush


3. Disinfect


4. Flush


5. Collect bacti samples

The results of a "grab" sample in a distribution system indicate

general potability

Your supervisor has instructed you to paint an existing pressure regulating station. You realize that this is a confined space and you know that you will have a problem with paint fumes. What will you do to protect yourself?

Use auxiliary ventilation and monitor the air.

Combustible gas detectors have an 'LEL" (Lower Explosive Limit) alarm setting of ________.

10%

When constructing a large well, the pump most used is a

submersible multi-stage vertical turbine pump.

Taste and odor problems are more noticeable

when the water is warm

According to the AWWA, about ________ percent of potable water supplied to a distribution is unaccounted for (due to leaks, bad meters, etc.)

5 - 10

The difference between the amount of chlorine added and the residual detected at a given point downstream in the water distribution system is called the

demand

Rising-stem valves are usually used

in pump stations

Dry barrel hydrants have their operating valves

in the base

To find the elevation of a pipe's "invert" (inside-bottom) an operator would

check the profile on the as-built

An example of a confined space would be a(n)

sewer manhole

After the disinfection process on a new water main, bacteriological samples are drawn and the water main is put into service

after the samples are found to be negative for coliform bacteria

You have a pump that raises water to a higher elevation reservoir. This pump has a normal discharge pressure of 115 psi and a normal flow of 2,300 gpm. On a routine check, you find that the pump has a discharge pressure of 162 psi and no flow. What would you suspect is the cause?

The tank filled up and the emergency altitude valve has shut off.

When talking about pumps, the term "semi-open" refers to _______ design.

impeller

While working in a chlorine station an operator got chlorine in his eyes, he should imediately

flush eyes with fresh water for 15 minutes

A piston pump operates on the _________ principal.

positive displacement

Some of all of the forces that a pump must operate against is known as

The total dynamic head

When entering a confined space, what % oxygen level is the minimum required for self contained breathing apprentice?

19.5%

The killing of pathogenic organisms in water is called

disinfection

When drawing a sample for bacteriological examination

leave space at the top for test medium

Bacteria that are know to be disease causing are called

Pathogens



The chemical used most for disinfection of water in the U.S. is

Chlorine

Sodium hypochlorite is

liquid chlorine

Water bearing geological formation is called

aquifer

One of the biggest problems with hyrogen sulfide gas is

de-sensitizes the nose

If the speed of a positive displacement pump is varied then

the flow with vary in direct relationship

The reducer installed in a centrifugal pump is called a

stabilizer

A Ventri meter detrims flow by measuring the pressure differencial

at the throat and a point just upstream of the throat

The most important reason to use a casing the first 50' feet of a well is

Prevent intrusion

A valve that joins a customer to a water main is called a

corporation stop

The maximum suction lift from a centrifugal pump is

34 feet

To determine is a sewer line crosses under or over a water line, you would look at

the profile view on the plans

The bend or goose neck is put in a water service line to allow

settling or movement of the soil

In well terminology, the term draw down means

the difference between the static water level and the pumping water level

Compound meters are used on service connections that have

a wide range of flows

Starting a centrifugal pump against a "closed" valve helps reduce__________ and ___________.

tuberculation / air pockets

If you find a coworker unconscious at the bottom of a confined space, you should

call for help immediately, but do not enter

The most common use for a gate valve is

as an isolation vavle

Plants give off vapor to the atmosphere in a process called

transpiration

Thrust is a condition that occurs in

any change of direction

If a pump operates at a suction head of ________, mechanical seals are recommended

60 psi

Fusible plug in a chlorine cylinder is designed to melt around ___________ to release pressure in a fire.

160 degree Fahrenheit

The most commonly used pump in the water distribution system is a

positive displacement pump

All vertical wall trenches 5' or deaper

require shoring

Blow off valves are installed on

the bottom of the water main to help drain it

Velocity in a water main is usually measured

in feet per second

Distribution system pressure should not be allowed to drop below

20 psi

The major cause of undue wear in a pump is

shift misalignment

Liquefied chlorine will vaporize to gas and expand to aproximatly

160 times its volume

Potable water lines should have at least _______ of horizontal separation from the sewer main

ten feet

The C factor of a water pipe is

the measurement of interior roughness

Hardness is water is caused by presences of

calcium and magnesium

The standard current signal output used by most analog measuring devices in the water industry is

4 to 20 MA

A common a very dangerous gas found in some confined spaces is

hydrogen sulfide

The type of pipe used for large water transmission mains is

concrete coated cement lined

In residential areas, isolation valves should be located at least every

1000 meters

"MCL" stands for

Maximum Contaminate Level

The maximum amount of water that can be withdrawn from a well continually over a period of time, which includes "the dries year", is referred to as the ___________ of a well.

"Safe Yield"

The number of bacteriological samples that a water supplier must take monthly is based on

the population and number of service connections