What are the three sides of the fire triangle? |
Oxygen, Fuel, Ignition Source |
|
Heat is produced when materials react how to form simpler compound? |
Exothermically |
|
This is the most appropriate type of detection for a computer room |
Air-Sampling smoke detection |
|
A condition where a burning fuel produces smoke without flames is known as what? |
Pyrolosis |
|
What kind of detector is most appropriate for an elevator lobby in an apartment building |
Spot-type smoke detector |
|
During UL tests, system-powered smoke detectors must respond to a polystyrene fire within how much time? |
2 minutes |
|
The horizontal spacing for a detector in a room with five minutes per air change is how many feet? |
25' |
|
Rooms or spaces with high ceilings may be subject to what condition during a fire |
Stratification |
|
What kind of detector is most appropriate for an unenclosed, unheated parking garage? |
Heat detector |
|
Concealed duct smoke detectors mounted more than 10' above the floor must be provided with what? |
Remote indicator |
|
Temperatures lower than 32℉ and higher than 100℉ are not suitable for these types of detectors? |
Smoke detectors |
|
Due to humidity and chlorine corrosion, smoke detectors are not suitable for rooms containing what? |
Swimming pools |
|
These detectors must cause a supervisory signal where the signal in annunciated at a constantly attended location |
Duct smoke detectors |
|
What kind of detector is most appropriate for an atrium? |
Projected-beam smoke detector |
|
When these are used for for releasing service, they must be installed on both sides of the protected door |
System smoke detectors |
|
Stair pressurization is an example of what? |
Smoke control function |
|
Duct smoke detectors are required when the minimum air flow exceeds what? |
2000 cfm |
|
Air-sampling smoke detector sampling pipes must be labeled every how many feet? |
20' |
|
Fan shutdown, smoke exhaust and stair pressurization are all examples of what? |
Smoke mitigation prevention |
|
Cigar smoke, diesel exhaust, and humidity in excess of 93% can cause what in smoke detectors? |
Nuisance alarms |
|
A type-A public emergency reporting system recorded more than how many alarms per year? |
2500 |
|
Before testing a protected premises system connected to a master box, what must be accomplished? |
Plug out the box. |
|
A public emergency alarm reporting system operates on what? |
100mA DC loop |
|
Central station service contract have what six elements? |
-Installation of the transmitters -Alarm, guards tour, supervisory and trouble signal monitoring -Re-transmission -Associated record keeping -Testing and maintenance -Runner service |
|
For a central service station, the prime contractor is in compliance if the system is what? |
Placarded and Certificated |
|
Central station operators must RE-transmit an alarm signal to the public fire dispatcher how quickly? |
Within 90 second |
|
What type of signal do public emergency alarm reporting systems provide? |
Alarm |
|
Proprietary supervising stations must retain records for not less than how long? |
12 months |
|
Runners must communicate with the supervising station at intervals not exceeding how long? |
15 minutes |
|
A chain of hardware stores under one ownership, a college campus under one ownership, and a military base are all examples of properties that are permitted to be monitored by what? |
Proprietary supervising station |
|
Single station smoke alarms for dwelling use became available in what decade? |
1970's |
|
The primary purpose of dwelling fire warning equipment is what? |
Life safety |
|
Areas of a dwelling more than how many square feet require additional smoke alarms or detectors? |
1000 ft |
|
The actuation of these is not allowed to cause the actuation of the following: a) alarms in other dwellings, b) other alarms within the same building, c) the building fire alarm system |
Multiple-station smoke alarms |
|
This is the most appropriate type of detection in dwelling garages, unfinished attics or crawl spaces? |
Heat detection |
|
Wall mounted heart detectors must be mounted so the top of the detector is between 4in and how many inches from the ceiling? |
12in |
|
Heat detectors mounted on the ceiling must be at least how many inches from the wall? |
4in |
|
What is the maximum number of unmonitored smoke alarms that can be interconnected? |
12 |
|
The NEC requires smoke alarms within how many feet of a range or cooktop to be either of the photoelectric type or to have a silence feature? |
21ft |
|
Dwelling heat detectors must be selected to operate at a temperature not less than how many degrees above the maximum expected ambient temperature in these protected space? |
25℉ |
|
Household fire alarm system must be provided with how many sources of power? |
2 |
|
Household fire alarm systems must have a secondary power source capable of providing not less than 24 hours of standby power followed by how many minutes of alarm? |
4 minutes |
|
A DACT on a dwelling fire alarm system must send a test signal to the supervising station how often? |
Monthly |
|
For alarm system controls in a one family home must conform to UL what? |
UL 985 |
|
Verification calls to a dwelling may be placed prior to re-transmitting the alarm, provided the delay caused by the call does not exceed how long? |
90 seconds |
|
Who is responsible for ensuring fire alarm systems are properly tested? |
The owner |
|
This must be provided to the owner or the owners representative upon completion of testing a fire alarm system? |
Site-specific software |
|
The owner must retain the record of inspection and test for how long? |
The life of the system |
|
The audibility of horns are tested using what? |
Sound pressure level meter |
|
How often do non-restorable, fixed temperature heat detectors need to be tested? |
Every 15 years |
|
NFPA 72 requires service personnel to be qualified and what? |
Experienced |
|
Control functions of control equipment not monitored by a supervising station must be tested how often? |
Annually |
|
This test is conducted upon completion of the initial installation of a fire alarm system? |
Acceptance test |
|
This test is required after any change is made to the fire alarm system? |
RE-acceptance test |
|
This test is conducted periodically to ensure system operability and reliability? |
Periodic |
|
Aerosol smoke, incense sticks, punk sticks, and so on are used on smoke detectors in this type of test |
Functional test |
|
Technicians who are factory trained for certain products are only qualified to work on what? |
Those certain products |
|
A single open circuit on this type of fire alarm circuit will cause a trouble alarm but will not affect the operation of appliances? |
Class A fire alarm circuit |
|
The minimum sound pressure level (SPL) required for a sleeping room which has an average SPL of 50dBA is what? |
75 dBA |
|
Heat detectors installed on a packed ceiling of a dwelling must be installed so they are how far from the peak? |
3' |