61 Cards in this Set
- Front
- Back
If a relay is used to initiate control of life safety function and is connected to a fire alarm system, it must be within what distance of the control circuit or appliance it is controlling? |
3 feet |
|
Which of the following is in the unacceptable method for conducting grounding conductors and bonding jumpers? |
Endothermic weld |
|
A connection to a grounding electrode conductor that is encased in a concrete or driven in the ground are ____. |
Not required to be accessible |
|
What type of cable shall be listed as having a fire restraint rating capable of preventing the advancement of fire from One floor to another and is listed for use in vertical run? |
CMR |
|
What is the minimal work space with in front of electrical equipment? |
30 inches |
|
What is the Max number of supervisory Initiating devices allowed on a single initiating device circuit? |
20 |
|
What piece of an electrical system carries or controls electrical energy as its primary function? |
Device |
|
What type of detector coverage will allow spacing requirements for detectors to be waived? |
Non required coverage |
|
Which of the following is not a symptom of heat stroke? |
Profuse Sweating |
|
Anton conductors for transiting stations attached to a building must be ___ Clear up surface. |
3" |
|
When using a UPS within a fire alarm system, the UPS must be in compliance with.... |
NFPA 111 |
|
The location of a circuit disconnect must be permanently identified at... |
The fire alarm control unit |
|
Which of the following is an allowable substitution for CATVP type cable? |
BLP |
|
What is the maximum number of bend in degrees Permitted in RMC between outlet boxes? |
360° |
|
When determining the spacing for smoke detectors on a flat ceiling, what spacing must be used as a guide? |
30' |
|
When are automatic smoke detectors required at NAC Extenders and supervising station transmitting equipment to provide smoke detection in that location? |
When areas are not continously occupied |
|
When mountain heat detectors on the ceiling they must be located no less than ____, Inches from the sidewall. |
4 |
|
What are the cables used in communication systems to ensure continued operation of critical circuit during a specific time under fire condition known as? |
Communication circuit integrity cable. |
|
Which of the following is not a requirement purpose of the fire alarm code as it is defined? |
Means of monitoring |
|
What is the minimum size ground in electrode wind made of pipe or conduit? |
3/4" |
|
When are automatic smoke tectors required to be placed above fire alarm control equipment? |
When areas are not continuously occupied |
|
At what dv level hearing protection required. |
92sBa |
|
What is the maximum rated output Allowed for a class one power limit circuit? |
Not more than 30V and 1000 volt amps |
|
According to the NEC and the electrical circuit that controls another electrical circuit through a relay is known as A. |
Remote control circuit |
|
Overhead collapse cables must have a vertical Clarence about roofs of not less than ____ feet. |
8' |
|
For the falling list of connectors, which type is prohibited for connecting a grounding conductor to an enclosure? |
Sheet metal screws. |
|
What type of optical fiber cable contains in electrical current caring conductors as well as optical fiber? |
Composite opposite fiber cable. |
|
The location of remote power supplies must be identified where? |
On the final drawing of record |
|
Grounding conductors for equipment shall be what color.? |
Bare green, green or green with one or more yellow stripes. |
|
If primary power is loss on an EVAC system and an FACP is activated by an alarm condition, how long must secondary power be capable of operating the voice evacuation system? |
15 minutes. |
|
Any event of normal power failure to a leavely required Stand By system, the Sandwich power must be available within _____ at a maximum. |
10 seconds. |
|
Any shot type auxiliary circuit, what is the smallest allowable conductor size? |
14 AWG |
|
Fuel cell systems use as a source of power must maintain a total of _____ hours of full demand operation. |
2 |
|
Which of the following statements correctly describes A design character is sick of video image detection systems.? |
1. Protection of settings from unauthorized changes 2. Perform base requirements 3. Prescribe base requirements. |
|
When remote indicators are required for use with duck detector, the indicators must be labeled with. |
The location of the associated duck smoke detector. |
|
When a raceway is run from the interior to the exterior of a building, The raceway shall ____. |
Be sealed with an approved material. |
|
The acronym ANSI represents |
American National Standards Institute |
|
What's the following is not a defined scope of the NFPA 72. |
When a fire alarm system is required. |
|
The national fire alarm and singling code is also known as? |
NFPA 72 |
|
If you are too install a new Messenger support wire in an area, you may do all of the following except? |
Attach to a preexisting Messenger wire if it is caring to sing type system cabling. |
|
The NEC is |
For the practical safeguarding of person and property. |
|
Which of the following conditions is not required to be met in order to Utilize speakers from an energy voice alarm communication system for a nom fire use? |
Audio level outputs must be reduced for not emergency signals. |
|
You are using a power tool that has a 3 prong plug. The only outlets available are 2 prong what can be done?? |
Locate a 3 prong plug or use a tool with 2 prong plug |
|
Which of the following allows optical fiber to be attached to the exterior of a raceway? |
Aerial spans to raceway type masts Intended for that purpose. |
|
Metal enclosures for grounding electric conductor shall be. |
Electrically continuous. |
|
Which type of detector is most suitable for protecting large openings like a gym? |
Linear beam |
|
Liquid type flexible middle conduit must not be used. |
We're subject to physical damage 💔 |
|
Exposed optical fiber's must be supported by the. |
Building structure |
|
Access to the proprietary station will be restricted to those persons directly concerned with the implementation and _____ of emergency action and procedure. |
Direction. |
|
Equipment must be engineered and tested to operate properly at _____ of its nameplate voltage |
85% |
|
What is the maximum length of a single ladder section? |
Thirty feet |
|
Fire alarm equipment must be designed and tested so that it is capable of performing at _____ nameplate voltage. |
110% |
|
Which article of the 2011 N FPA 70 specifically covers fire alarm system wiring. |
760 |
|
Visual appliances are required in area if the average ambient sound level is greater than the level of what? |
105 dBa |
|
Which is the following statements correctly? Complete the following sentence combination with manual fire alarm boxes and guarding signal stations _____. |
Must be permitted |
|
Which of the following terms best describe the following phrase? In the electrical circuit that is used to energize signal equipment. |
Signaling circuit. |
|
Electrical insulation that are installed with compliance to the electrical code are essentially ______. |
Free of hazard |
|
Aman's inspection will include verification that the release and circuit and component energized by the FACP are _____ and operate properly in alarm condition. |
Electrically supervised |
|
Plenum optical fiber raceways must be listed as having ample fire Resistance and low _____. |
Smoke producing characteristics. |
|
A Metal water pipe that runs underground can serve as a grounding electrode if it is direct contact with the Earth for at least ______ or more. |
Ten feet |
|
What is the Max number of Waterflow Switches that are permitted to be connected to a single initiating device circuit? |
5 |