If a critically charged refrigeration system is overcharged, which of the following is a likely result?

Increased operating pressures

The approximate condensing temperature for R22 on a 95 degree day is _______ and the head pressure will be ________.

125°F, 278psig

If an air conditioning system is calling for cooling and the compressor is running but the indoor (evaporator) fan is not running, which terminal on the thermostat will the technician most likely check first?

G terminal

A 120 volt / 24 volt control transfer has a VA read rating of 20. The maximum amperage the Transformer will put out is 0.8 amps. True or false?

True

Technician "A" says that while checking the windings of a compressor, a reading of 10 ohms or less from the common terminal to ground indicates that the motor is okay. Technician "B" says that the resistance of the start winding should always be less than the resistance of the Run winding. Which of the following statements is correct?

Technician A is incorrect, technician B is incorrect.

If the resistance of the Run winding decreases:

The motor will draw too much current while it is running.

What voltage does a potential relay operate from?

The back EMF induced in the start winding.

When the compressor in a system using capillary tubes is sweating, it is a sign of:

Any of the above

On a 95-degree day, the R22 refrigerant pressure on the high side of a high-efficiency system should be about _______ psig.

243

The instrument to check for a short in the compressor motor winding is:

An ohmmeter

The best way to tell if a compressor discharge line is at the correct temperature is to grab a hold of it. True or false?

False

With a rise in outdoor temperature, the head pressure will rise. True or false?

True

Reducing the CFM through the evaporator will cause the head pressure to_________.

Decrease

If the suction pressure of an R-22 air conditioning system is 67p Sig and the evaporator Outlet temperature is 51 degrees, what is the evaporator superheat?

12 degrees

What does poor air flow across the evaporator cause?

All the Above

A high superheat reading in a system that has a TXV indicates the TXV is defective. True or false?

False

A normally open switch when closed will show:

Both B & C

After evacuation, refrigerant in the liquid form is normally put into the system through the:

Liquid line

If an air conditioning system is turned on but none of the major components (compressor, condenser, indoor fan) are operating, what is the first thing that a technician should check?

The power being supplied to the system.

If line 1 of a circuit had a potential of 120 volts and line 2 has neutral, the potential voltage difference between Line 1 and line 2 would be 0 volts. True or false?

False

A technician needs to check a single phase compressor. He labels the three terminals a, b and c and takes resistance readings of the windings. He reads 10 ohms from A to B, Infinity from B to C and infinity from C to A. Identify the terminals.

Can I identify terminals; open winding

If a motor hums but does not start, there is a potential problem with:

All the Above

Three terminals in the compressor junction box are marked 1, 2 and 3. Using an ohmmeter, the resistance of the internal motor windings are: 1.5 ohms between terminals 1 and 2, 3.5 ohms between terminals 1 and 3 and 5 ohms between terminals 2 and 3. The common terminal is:

One

If an air-cooled condenser is located on a 95 degree roof and the condenser saturation temperature is 150 degrees, which of the following is a possible scenario?

Both A & B

As a rule of thumb, the air leaving the evaporator will be about ________ than the air entering the evaporator.

18 to 22 degrees cooler

On a 85 degree day, the R22 refrigerant pressure for a high-efficiency condensing unit should be about ________ psig.

211

Problems in the refrigerant portion of a system are caused by:

Any of the above

If the metering device malfunctions and gets stuck in the closed position, the compressor could overheat. True or false?

True

Subcooling occurs in the evaporator as well as the condenser. True or false?

False

Reducing the CFM through the evaporator will cause the amount of moisture removed from the air to ________.

Increase

How would too much refrigerant affect the operation of a system with capillary tubes?

Raise the head pressure and suction pressure, reduce superheat and reduce system capacity.

How does a dirty condenser affect a capillary tube system?

Poor cooling, High head and high suction

The most common cause for an evaporator to freeze is:

Dirty air filter

When working on an air conditioning or heating unit the technician always needs to remember?

All the Above

When charging a system with Vapor refrigerant from a refrigerant cylinder the cylinder will become:

Cold

The term volt-ampere (VA) is used to:

Determine how much current can flow through a Transformer at a given voltage

The cooling anticipator in a thermostat is usually an adjustable type. True or false?

False

Technician "A" says that a shorted winding will result in an increase current flow through the winding. Technician "B" says if a motor is to be replaced a motor with a lower horsepower rating should always be used. Which of the following statements is correct?

Technician "A" is correct, technician "B" is incorrect

An open winding in an electric motor means that:

A wire in the winding is broken

If a condenser fan motor grounds out, it will usually:

Trip a circuit breaker to shut off the unit

Condensing units located outside that are required to operate year-round must have:

Head pressure control

If a compressor motor locks up it will:

All the above

The liquid line temperature is used to determine the ________ of a condenser.

Subcooling

A typical evaporator superheat reading at the evaporator outlet for a central air conditioning system on a 95 degree day would be ________ degrees F.

8 - 12

If a compressor has a partially shorted winding, it could run for a while, overheat and shut off. True or false?

True

Reducing the CFM through the evaporator will cause the amperage draw of the compressor to ________.

Decrease

Two types of fixed bore metering devices are ________ and ________.

Capillary tube and pistons

In any fashion compressor is usually indicated by ________ head pressure and ________ suction pressure.

Low, high

If a system is overcharged the discharge pressure will?

Increase

The use of fuses for troubleshooting is an acceptable practice. True or false?

False